Short answer
Do a UL-rated wall takeoff by its assembly, not its length: find the UL design number for each partition type, count the board layers on each side, and multiply linear feet by height to the deck by total layers. Carry Type X and Type C as separate lines, then add rated head-of-wall joints and waste.
A drywall takeoff for UL-rated walls starts from the assembly, not the length, because a rated wall costs more than its length suggests. The rating sets how many layers of board go on each side, which board type, how high the wall runs and what happens at its head. Price it from the linear footage of a non-rated partition and the bid is short before labor is counted. This guide follows a rated wall from the partition schedule to a sheet count.
What is a UL design?
A UL design is a tested wall, floor or ceiling assembly listed in UL's fire-resistance directory under a number such as U419. The listing names the studs, the board type and layers, the fasteners and the joint treatment that earned the rating. Build anything different and the rating does not apply, so the takeoff follows the listing line by line.
01Find the UL design on the partition schedule
Every rated partition on the drawings should trace to a tested assembly. The partition schedule (or wall-type legend) gives each type its tag, stud size and gauge, the board on each side, the rating and, on a well-drawn set, the UL design number it was built to, such as a U419 or U465 steel-stud design.
Check three places before you measure anything:
- The partition schedule for each type's layers, board and design number.
- The life safety or code plan for which walls are rated: corridors, exit stairs, tenant demising walls and occupancy separations.
- The 09 21 16 spec section for the board manufacturers it allows and any Type C requirement.
A schedule that gives a rating ("1 HR") with no design number does not tell you the layers. Write it down as a question for the architect before bid day, and state the assembly you priced in your proposal. A wall tagged as a non-rated type on the floor plan but drawn as rated on the life safety plan is the same kind of conflict.
02Count the layers on each side
The design number decides the layers, not the rating alone. For common non-load-bearing steel-stud designs, the pattern usually looks like this, but read the listing for the design you are building:
| Rating | Typical steel-stud assembly | Layers in the takeoff |
|---|---|---|
| 1 hour | One layer of 5/8 in. Type X each side | 2 |
| 2 hour | Two layers of 5/8 in. Type X each side | 4 |
| 3 hour and up | Varies by design: read the listing | per the design |
Some designs reach the same rating with fewer layers of a proprietary board, and shaft walls are built from one side with shaftliner, so they get their own takeoff. That is why the count follows the design, never a rule of thumb.
The board area for one wall type is:
board area = linear feet × height × layers per side × sides
A wall rated from one side only, such as a furring wall against a rated shaft, has one side in that formula.
03Carry Type X and Type C as separate lines
Type X is the standard fire-resistant board, defined in ASTM C1396 by how it performs in a standard test assembly. Type C is an enhanced fire-resistant board, with more glass fiber and additives that keep it from shrinking and cracking at high heat. Each manufacturer sells its own Type C product, and designs list the products they were tested with.
What that means for the takeoff:
- You cannot swap Type X in where the design calls for Type C.
- Some designs accept only named products, which narrows your supplier quotes.
- Type C most often shows up in rated ceilings and soffits, column and beam enclosures, and some multi-hour designs.
Keep each board type on its own line with its own unit price. A takeoff that lumps "5/8 in. fire-rated" together cannot be priced or checked.
04Run rated walls to the deck, not the ceiling
Most rated walls continue above the ceiling to the floor or roof deck. The building code requires fire barriers to extend to the underside of the deck above, and most fire partitions do too, with limited exceptions. On a tenant improvement with a 9 ft 6 in. ceiling and a 13 ft 6 in. deck, measuring a rated corridor wall to the ceiling misses about 30 percent of its board on every layer.
Take each rated type's height from the sections and the reflected ceiling plan, and note where a wall changes height (a soffit, a raised ceiling, a sloped deck).
05Count the head-of-wall joints and control joints
Where a rated wall meets the deck, the joint needs a listed head-of-wall system that lets the deck move without opening a path for fire. These systems are tested under UL 2079 and usually combine deflection track with a listed firestop sealant or spray. Count them in linear feet along the top of each rated wall.
Decide who carries the head-of-wall firestopping, you or the firestop subcontractor, and say so in your inclusions and exclusions. Rated control joints are another linear-foot line, with their own listed detail.
06Count sheets wall by wall, then add waste
Dividing the board area by 48 and adding a waste factor is how a rated bid comes up short. Square feet assume every inch of every sheet goes on a wall; a 13 ft 6 in. wall does not divide into 4 x 12 sheets, so the order leaves you short on the job and long on strips nobody can use.
Count sheets the way the wall will be hung:
- Pick the sheet length and direction for each wall height, where the UL design allows either. A 13 ft 6 in. wall takes 4 x 14 sheets hung vertically, with 6 in. cut from each, or 4 x 12 sheets hung horizontally in three full courses and a 1 ft 6 in. strip course.
- Count sheets per wall, per side, per layer, from the wall length and that layout. Offset the face layer's joints from the base layer's as the design requires.
- Add waste for damage and miscuts on top of the count. 10 percent is a common default; set yours from what your finished jobs actually used.
Keep each board type and sheet length on its own line, so the supplier quote matches what goes up.
Worked example: two rated types on an office TI
An office tenant improvement with a 13 ft 6 in. deck and a 9 ft 6 in. ceiling has two rated partition types, in 30 ft walls. The design allows vertical application, so the board is 4 x 14 sheets, 8 per wall side per layer (30 ft ÷ 4 ft, rounded up), plus 10 percent waste. The numbers are an example.
| Type | Assembly | LF | Height to deck | Layers | Board (sq ft) | 4 x 14 sheets with waste |
|---|---|---|---|---|---|---|
| P3, 1-hour corridor | 1 layer 5/8 in. Type X each side, 3-5/8 in. studs | 180 (6 walls) | 13 ft 6 in. | 2 | 4,860 | 96 + 10% = 106 |
| P5, 2-hour separation | 2 layers 5/8 in. Type X each side, 3-5/8 in. studs | 60 (2 walls) | 13 ft 6 in. | 4 | 3,240 | 64 + 10% = 71 |
| Total rated board | 240 | 8,100 | 177 |
Ordered by square feet, the same walls come to 8,100 ÷ 48 × 1.10 = 186 sheets of 4 x 12, which do not reach a 13 ft 6 in. wall hung vertically at all. Measured to the ceiling instead of the deck, they come to 5,700 sq ft, 2,400 sq ft short before waste. The head-of-wall joint line is 240 LF, one for each foot of rated wall.
Common mistakes on rated walls
- Measuring rated walls to the ceiling. Most run to the deck, and the missing height is missing on every layer.
- Ordering by square feet. Area ÷ 48 plus waste ignores sheet length and layout; count sheets per wall.
- Lumping Type X and Type C. One "fire-rated board" line cannot be priced against the design or checked by the GC.
- Pricing a rating with no design number. "1 HR" does not tell you the layers; ask, and state the assembly you priced.
- Skipping the head-of-wall joints. Every foot of rated wall that meets the deck needs a listed joint, and someone has to carry it.
- Missing an addendum that changes a type. A wall that becomes rated in an addendum changes its layers, height and joints; re-price the lines it touches.
Questions estimators ask
- How many layers of drywall are in a 2-hour wall?
- In common non-load-bearing steel-stud designs, two layers of 5/8 in. Type X on each side, four layers in total. Some designs reach 2 hours with fewer layers of a proprietary board, and shaft walls use shaftliner from one side, so the UL design number decides.
- Is Type C required for a 2-hour wall?
- Only if the UL design you are building calls for it. Many 2-hour steel-stud designs use Type X. Type C shows up most in rated ceilings and soffits, column and beam enclosures, and some multi-hour designs. You cannot substitute Type X where the design lists Type C.
- Do fire-rated walls have to go to the deck?
- Usually. Fire barriers extend to the underside of the floor or roof deck above, and most fire partitions do too, with limited exceptions. Take each rated type's height from the sections and the life safety plan, not from the ceiling height.
- Who carries the firestopping at the head of a rated wall?
- It depends on the scope split on the job: the drywall contractor or a firestop subcontractor. Include the head-of-wall joints in your takeoff, in linear feet, either way, and name who carries them in your inclusions and exclusions.
Sources
- Peterson & Dagostino, Estimating in Building Construction, 9th ed. (Pearson, 2019), §17-3 Types of Assemblies
- Peterson & Dagostino, Estimating in Building Construction, 9th ed. (Pearson, 2019), §17-4 Drywall Types
- Peterson & Dagostino, Estimating in Building Construction, 9th ed. (Pearson, 2019), §4-8 Materials
- UL Product iQ: fire-resistance design listings (BXUV)
- Gypsum Association, GA-600 Fire Resistance and Sound Control Design Manual
- ASTM C1396, Standard Specification for Gypsum Board
- UL 2079, Tests for Fire Resistance of Building Joint Systems
- International Building Code, Sections 707.5 and 708.4 (continuity of fire barriers and fire partitions)
- ASTM C754, Standard Specification for Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products
- ASTM C840, Standard Specification for Application and Finishing of Gypsum Board